ARERA approves Terna's Allegato A.40 update setting behavior rules for non-dedicated storage in Italy's upward modulation service
DecisionARERA (Delibera 419/2026/R/eel, 10 Nov 2026) verified the regulatory conformity of Terna's proposed amendment to Allegato A.40 of the Codice di Rete, which sets technical behavior requirements for energy storage systems located at sites contracted for the 'modulazione straordinaria istantanea a salire' service but not explicitly committed via maximum-discharge command ('sistemi di accumulo non asserviti').
The decision extends the same compliance logic applied to generation units (no output reduction during modulation events) to non-dedicated storage assets, requiring them to hold steady power exchange for at least 15 minutes (or until stored energy is exhausted) and to share active power, interface breaker status, and maximum deliverable energy data with Terna. This closes a technical gap in the TIDE framework's ancillary/balancing service rules as storage penetration grows, affecting how storage assets are monitored and credited for correct service delivery within Italy's dispacciamento system.
This is a narrow but consequential technical-rule decision within Italy's broader TIDE (Testo Integrato del Dispacciamento Elettrico) reform. It follows the established regulatory pathway: Terna proposes Codice di Rete annex changes, consults the market, and submits a final proposal for ARERA's conformity verification under deliberazione 345/2023/R/eel's governance framework. The specific issue addressed—how to treat storage systems co-located at modulation-contracted sites but not formally dedicated to the service—reflects the practical complexity of integrating flexible storage assets into legacy ancillary-service verification methodologies originally designed for generation units. By mandating comparable behavioral obligations (sustained power exchange, data transparency) while allowing exceptions tied to limited energy availability, ARERA and Terna are calibrating performance verification to storage's physical constraints rather than applying generation-unit rules uniformly. This matters for storage operators' exposure to non-compliance penalties and for Terna's ability to accurately assess whether modulation events achieve their intended system security purpose. It is a incremental refinement rather than a structural market redesign, but it sets a precedent for how non-dedicated flexible resources will be treated as DER penetration increases under TIDE's phased implementation (transitional phase through Jan 2026, consolidation phase from Feb 2026, and an as-yet-undated 'regime' phase).
TIDE - Testo Integrato del Dispacciamento Elettrico (Allegato A alla deliberazione 345/2023/R/eel, v.4 per deliberazione 227/2025/R/eel); Codice di Trasmissione, Dispacciamento, Sviluppo e Sicurezza della Rete, Allegato A.40; ARERA Delibera 419/2026/R/eel; preceding deliberazioni 564/2023, 572/2023, 483/2024, 364/2025/R/eel
—
Primary sources
419/2026/R/eel — Verifica di conformità delle proposte di modifica al Codice di Trasmissione, Dispacciamento, Sviluppo e Sicurezza della Rete in materia di servizio di modulazione straordinaria a salire
Open primary source ↗